BALL VALVE CLASSIC F X F
KV 992M - KV 995M
The basic version is available with internal threads and a metal handle.
Other versions with:
- hollander connector,
- external / internal thread.
Category:
  • USAGE
  • DIMENSIONS
  • QUALITY
  • TEHNICAL DATA
  • INSTALATION
  • DOKUMENTACIJA

HERZ ball valves have to be used as shut off elements. Field of application are building services, such as heating or chilled water plants. Ball valves are used wherever the medium flow has to be reliably closed. Ball valve should not be used as regulating element so it has to be fully opened or fully closed (the handle should not be in intermediate position
art. ident ean DN PN G L C B H1 SW
KV 992M 1122071 3838963237839 15 25 G1/2" 44,6 11 60,6 40,4 25
KV 993M 1132071 3838963237846 20 25 G3/4" 51,9 11 60,6 42,6 30
KV 994M 1142071 3838963237853 25 25 G1" 63,6 14 85 60,1 38
KV 995M 1152071 3838963364849 32 25 G1-1/4" 74 15 85 63,9 47
Operating data
  • Operating pressure: max. 25 bar
  • Operating temperature range: -10°C to +110 °C, (water +0,5 °C to +110 °C - no steam)
  • Medium: water (non-aggressive media)
Heating water quality according to ÖNORM H5195 or VDI- Standard 2035. The use of ethylene or propylene glycol in amixing ratio 25- 50% is allowed. Please refer to manufacturers documentation when using ethylene glycol products forfrost and corrosion protection. Please note that EPDM gaskets will be affected by Mineral oils lubricants and thus lead to failure of the EPDM seals in the valves that use EPDM seals. The HERZ ball valve for heating and chilled water is not suitable for usage of agressive medium (such as: acids, alkalis, combustible and explosive gases..) because it can destroy sealing components
Assembly instructions

The threads of the pipe have to be coated with a suitable sealing material (spinning material, Teflon ribbon, sealing paste). There should not be excess of sealing material on the pipe because it can damage the thread. The ball valve with thread (G, R) is screwed onto the pipe. The pipes have to be correctly alligned, so the valve is not loaded with a bending moment. When using cooper or plastic pipes take into account pressure and temperature limits of used material. When assembling, use a suitable assembly tool that adapts to valve end connections (Sw, Sw1). The ball valve can be mounted in any position: horizontal, vertical or upside-down. Following assembly, the connections of ball valve must be checked for water-tightness by the installer. All engineering standards and recognised regulations must be adhered by these specialist staff. If there are impurities in the medium (water too hard, dust, etc.) there should be a filter installed, in other case the impurities can damage the seals in the valve.

According to EN 806-5 (point 6. Operation) valves should always be in their fully opened or closed position and actuated at regular intervals to ensure they remain operational. Therefore HERZ Ball valves must be closed and opened for several times periodically every six months. This prevents the ball valve from blocking, reduces sediment deposition and reduces the possibility of corrosion inside the valve.